Special Process & OEM Steam Boiler

CAS
Special Process & OEM Steam Boiler
  • Steam Pressures to 90 psig (Optional trim of 15, 30, and 50 psig available).
  • Steam Capacity (48 - 60 Lbs/Hr @ 0 - 90 psig)
  • 16 - 20 kW (55 - 68 Mbh)
  • 208, 240 and 480 Volt, 1 & 3 Phase (600V Available)
  • ASME Section I Code “M” Pressure Vessel Carbon Steel (100 psig) (CRN Available)
  • 0.430 Dia. Copper Sheath Heating Elements
  • Two Pressure Controls — Operating and Automatic Reset High Limit
  • Electronic Water Feed Control with Low Water Cutoff (Dual Probe)
  • Automatic Solenoid Water Inlet Valve with In-line Check Valve
  • Water Level Sight Glass and Blow Down Drain Valve
  • Pressure Gauge (0 - 160 psig)
  • ASME Safety Relief Valve
  • Third-party certifications: UL Listed, CSA, M

CAS Steam Boilers- are specifically designed for use where space requirements are limited. The compact construction and low profile permit the CAS boiler to fit under hospital and research laboratory steam sterilizers. CAS boilers are easily adapted to garment presses, dry cleaning and other textile equipment. With an optional solenoid actuated steam gun, the CAS becomes a perfect tool for shrink fitting upholstery fabrics in furniture and automobile after market industries.

CAS boilers are also used in food, plastics, rubber and pharmaceutical processing.

All CAS boilers are inspected to rigid quality standards. They are factory tested under actual operating conditions and are ready to operate.

Pressure Control easily adjusts operating pressure.

Steam Pressure Gauge provides visual indication of steam pressure.

On/Off Switch with Pilot Light indicating boiler is energized and operational.

Water Level Sight Glass allows constant visual observation of boiler’s water level.

Automatic Solenoid Water Inlet Valve can be connected directly to water main, eliminating complicated feed water piping4. Integral control relay (rated 1/3 Hp 120V) for external high pressure water feed pump and motor.

Electronic Water Feed Control Probe is located in an isolator tube to assure true boiler water level readings during operation.

Safe, Reliable Operation assured by a low water cutoff that shuts down the boiler if it accidentally runs low on water.

Select a Part
Part # Description  
025283 CAS-20CM 480V 20KW 3PH W/ Buy Now
109217 CAS-20-CM 208V 3PH 20KW W Buy Now
109225 CAS-20-CM 240V 3PH 20KW,W Buy Now
Can't find what you're looking for?