Hazardous Location Immersion Temperature Junction

80016
Hazardous Location Immersion Temperature Junction
  • Explosion Resistant Junction Box
  • Non-Indicating
  • Heliarc Welded Thermowell
  • Tolerates Extreme Temperature Exposures
  • 10 Amps at 120 Vac,
    5 Amps at 240 Vac
  • Third-party certifications: UL Listed, CSA

The 80016 is an assembly consisting of a Series 17000 or 47000 unit, well assembly, and explosion-resistant junction box designed to meet the requirements of Class I, Group D, and Class II, Group E, F and G, Division 1 and 2 locations.

The sensing element, which is a cartridge-type unit, is seated in the well assembly, and held in place by a snap ring. The well assembly, in turn, is threaded into the explosion-resistant junction box, giving protection to the controller.

Not recommended for pilot duty switching of magnetic contactors.

Well Assembly Pressure Ratings 100 psi at 250˚F (690 kPa at 120˚C)
60 psi at 500˚F (415 kPa at 260˚C)
Well Assembly Material Type 321 Stainless Steel
Current Rating 10 Amps at 120 Vac
5 Amps at 240 Vac
Extreme Temperature Exposures May be exposed to -100˚F (-74˚C) indefinitely. They may be exposed to high temperature for one hour maximum as follows:
Model Exposure
80016-17000 100˚F (55˚C) above setpoint
80016-17021 500˚F (260˚C)
80016-47002 100˚F (55˚C) above setpoint
80016-47023 600˚F (315˚C)

Select a Part
Part # Description  
305250 80016-17000 100 TO 400 F Buy Now
305269 80016-17021 -100 TO 400F Buy Now
305277 80016-47002 -100 TO 500F Buy Now
305285 80016-47023 -100 TO 500F Buy Now
Can't find what you're looking for?