Features
- Small Enclosure. The 6.25 inch by 6.25 inch
enclosure houses the temperature control
and monitoring unit along with terminals for
connecting instrument power, heating cable
and RTD.
- 100 Ohm platinum RTD which can be pipe
mounted or can be used to sense ambient air
temperature.
- Pipe stand-off mount for direct pipe mounting.
- Integral wiring. The wiring of the heating cable,
alarm, AC power line and the RTD sensor are
all accomplished within the enclosure. This
feature reduces both labor and material costs
by eliminating the need for an additional heat
trace power connection kit as well as the time
for the additional wiring.
Applications
- Freeze Protection of Piping
- Hot Water Temperature Maintenance
- Grease Waste Flow Maintenance
Environments
Sensors
- 100 OHM PT RTD
- Probe Length = 4" (10.2 cm)
- Probe Diameter = 1/4" (6.35 mm)
- Leadwire Length = 3ft (1 M)*
* The maximum allowable length of the RTD
wire is 50ft (15m) in order to remain UL/cUL
compliant.
Current Approvals
The CET-GF electronic thermostat with ground fault is a control and power connection kit. It is used for freeze protection or process temperature maintenance of pipes or tanks protected by heat tracing products. This thermostat can be used with CPR, CPM, CZH and CMi heating cables in Ordinary area locations.
This unit is designed to provide local temperature control and monitoring for heat traced pipes or tanks across a variety of industries and applications and will switch 30 amperes of current.
The CET-GF provides easy programming of the temperature set point, high and low temperature alarms, the deadband, the temperature units, the soft start function and the alarm state through the front panel push buttons. LED lights are provided for indication of power to the unit, heater power on (load) and alarm status. A Form C dry contact alarm is included for wiring to your building management system to indicate alarm status. This alarm may be set to open or close on all alarm conditions including loss of power, high or low temperature alarm and RTD failure. Choose either the DC or the AC customer supplied voltage alarm variation. The minimum operating ambient temperature is -40°F (-40°C). This unit has programmable high and low temperature alarm set points from 20°F (-6°C) to 230°F (110°C).
A 100 Ohm platinum RTD is provided with a 3 foot (1 M) lead resulting in flexible mounting options for the user.